Meter fault detected during the inspection – issuance of short assessment bill – P/272/2012 – Abdul Nazar P.I., Kakkanad, Ernakulam.
The APTS inpection revealed that one of the metering CTs was not working and the other two CTS were also not measuring the consumption correctly. The test conducted with a standard test meter “ACCUCHECK” showed that the error of the meter was 89% of the actual energy consumed. The case settled with the consent of the consumer, by agreeing to assess him for 89% energy loss for the last one year and hence ordered to revise the short assessment bill accordingly.